In September 2009 Blackburn Starling was awarded formal certification against Quality
Management Standard BS EN ISO 9001:2008 for our Design and Manufacturing activities, by the British Standards Institute.
As our ability to provide software for integrated monitoring and control
applications became a core business activity the Quality Management system
was enhanced. This was formally recognised by the award of another Quality
Management Certificate against the requirements of BS EN ISO 9001:2008 TickIT. This is a specialist certification scheme covering specifically the
development, supply and maintenance of software.
Click below to view our certificates and their applicable scope.
|
Electrical Design and Manufacture
|
Software Development
|
|
|
|
Achilles UVDB Verify
Following an audit by the Verify Team in November 2003 Blackburn
Starling is now an approved Verify Supplier. The
certificate details the standards achieved following the up to date assessment of
our Safety, Health, Environmental and Quality practices and procedures in November
2009.
Blackburn Starling is registered as an approved supplier for:
|
 |
|
 |
|
|
Supplier No.73619 |
Supplier No.73619 |
Supplier No.10043168 |
Supplier No.19847
|
Achilles Carbon Reduction Scheme (CEMARS)
Blackburn Starling is a member of the Achilles Certified Emissions
and Reduction Scheme. The
certificate and
disclosure statement details ISO 14064-1 compliance.
ASTA Certification
All products manufactured by the company are independently tested and comply
with the International Standard EN 60439.1 (IEC 439.1) & EN 60298. These standards
lay down a comprehensive package of performance that must be verified
in order to satisfy the requirements of fully Type Tested Assemblies (TTA).
These tests come under eight basic headings as:-
- Temperature Rise Limits
- Mechanical operation tests
- Dielectric Properties
- Short-circuit withstand strength of the main circuits
- Short-circuit withstand strength of protective circuits
- Effectiveness of protective circuit
- Clearance and creepage distances
- IP degree of protection
|
Type Test
Certificates - ASTA, TUV |
|
Cert. No. |
British Standard |
Date of Test |
Description |
|
7963 |
BS4070:1966 |
June 1975 |
Modular Control Board Busbar System 1600A
45kA, 3s. 112kA Peak (Bars = 2/ph & 1/N) |
|
8769 |
BS5486:Part 1:1977
IEC 439:1973 |
Aug 1980 |
1600A FBA Busbar System
71kA, 1s. 156kA Peak |
|
8773 |
BS5486:Part 1:1977
IEC 439:1973 |
Aug 1980 |
800A FBA Busbar System
50kA, 1s. 105kA Peak |
|
8785 |
BS5486:Part 1:1977
IEC 439:1973 |
Sept 1980 |
1600A FBA Busbar System
50kA, 3s. 112kA Peak |
|
9132 |
BS5227:1975
Clause 26 |
Dec 1981 |
12kV - Busbar Trunking
3 - 101.2 x 6.35mm, 50kA,3s, 125kA peak
28kV, 1 min power frequency withstand voltage |
|
9133 |
BS5486:Part 1:1977 |
Dec 1981 |
FBA Busbar System
3000A & 2500A and 630A Starter
50kA, 3s. 105kA Peak (Bar = 3/Ph & 2/N) |
|
9802 |
BS5486:Part 1:1977 |
May 1984 |
Supplementary cert. to 8773, for outgoing circuits. |
|
9858 |
BS4941: Part 1:1979 App C, Clause 6. |
Feb 1984 |
Starter co-ordination type “C” |
|
11440 |
BS5486:Part 1:1986
IEC439-1:1985 |
Jun 1990 |
FBA Busbar System 51
x 6.35mm - 50kA, 1s. 105kA peak
25.4 x 6.35mm - 25kA, 1s. 52.5kA peak |
|
11463 |
BS5486:Part 1:1986
IEC439-1:1985 |
Jun 1990 |
FBA Busbar System
80kA, 1s. 176kA peak 2
x 76.2 x 6.35mm |
|
12744 |
BS EN60439-1:1994
IEC 439-1:1992 |
Jun 1995 |
FBA Busbar System
80kA, 1s 176kA peak 2
x 152.4mm x 6.35mm |
|
12745 |
BS EN60439-2:1993
IEC 439-1:1992 |
May 1995 |
Busbar Trunking
80 kA, 1s. 176kA peak
2 x 152.4mm X 6.35mm |
|
Test Report 1668 |
BS 159:1992 |
Feb 1996 |
Cable link box. 16kA, 1s.
40kA peak
28kV, 1min, power frequency withstand voltage
75kV lightning impulse withstand tests |
|
12915 |
BS EN60439-1:1994
IEC 439-1:1992 |
Mar 1996 |
FBA Busbar System
50kA, 1s. 105kA peak 3
x 101.6 x 6.35 mm
3 x 76.2 x 6.35 mm
2 x 76.2 x 6.35 mm
1 x 50.8 x 6.35 mm |
|
12928 |
BS EN60439-1:1994
IEC 439-1:1992 |
Apr 1996 |
FBA Busbar System
80 kA, 1s. 176kA peak 3
x 152.4 x 6.35mm |
|
Report of Performance No. 6328-02 |
|
Apr 1996 |
Prospective rated internal fault arcing current
80 kA, 0.1s. 176kA peak |
| 14439 |
BS
EN60439-1:1999 |
Feb
2000 |
50
kA, 1s, 105 kA peak, 1 - 50 x 6mm Vertical Busbar, 1 - 50 x 6 mm
Horizontal Busbar, 1 - 100 x 6mm Horizontal Busbar. 1 - 50 x 6mm ACB Connections and ISOVAL TM support straps |
| 14482 |
BS
EN60439-1:1999 |
May
2000 |
50
kA, 1s, 105 kA peak, 1
x 50 x 10mm Horizontal Busbar, 1 x 50 x 6mm
Vertical Busbar, 1
x 160 x 10mm Horizontal Busbar, 1 x 50 x 10mm ACB Conns, Vertical Bars &
Incoming palms. 80kA, 1s.
176 kA peak, 2
x 100 x 10mm Horizontal Busbars. |
| 14487 |
BS
EN60439-1:1999 |
Sep
2000 |
1 - 100 x 6mm 50
kA, 1s. 105kA peak, 3 Ph. 30 kA, 1s. 63 kA Peak Ph-N. 1 -
50.8 x
6.35mm, 30 kA, 1s. 63 kA peak P-E.
2 x 50.8 x 6.35mm, 48 kA, 1s. 100.8 kA peak P-E |
|
14904 |
BS
EN60439-1:1999 |
May
2001 |
100
kA, 1s. 230kA peak, 3 Ph. 60 kA, 1s, 132 kA Ph-N / Ph-E. 2 x 200
x 10mm Horizontal Busbar. 1 x 120 x 10mm Feeder Vertical Busbar. 3 x 100 x 10mm ACB Connections. 3.5kV dielectric test. |
|
14905 |
BS
EN60439-1:1999 |
May
2001 |
2 x 160 x 10mm Horizontal Busbar & 400A 4P ACB through fault. 80kA,
1s. 200 kA Peak, 3 Ph.
80kA, 1s. 176kA peak Ph-N. 60 kA, 1s. 132kA Peak, Ph-N / Ph-E.
Conditional SC test on Fuse & Fuse switches - 32A, 63A, 100A, 200A,
400A @ 50kA. |
|
XZ 232 F 01 |
IEC 60298, 3rd Ed
1990-12 |
Apr 2002 |
5 x 10mm busbars @
33.4kA, 3s, 82.9kA peak Earth Switch @ 25.9kA, 1s, 64.5kA peak. |
|
XZ 232 F 02 |
IEC 60298, 3rd Ed
1990-12 |
Apr 2002 |
VCB & cable box @
31.5kA, 3s, 84kA peak. Earth Switch @ 41.6kA, 1s, 104kA peak. 5 x
10mm VCR riser @ 51.1kA, 1s. 127kA peak. 100 x 10mm busbars @
52.2kA, 3s. 127kA peak. |
|
XZ 232 L02 |
IEC 60298, 3rd Ed
1990-12 |
Apr 2002 |
4 panel MV switchboard
Arc fault containment to Annex AA, 25kA, 1s. |
|
TZ 185 Z 01 |
IEC 60290, 3rd Ed
1990-12
IEC 60694, Ed 2.2, 2002-01 |
Apr 2002 |
4 panel MV switchboard
75kV lighting impulse withstand test 28kV power
frequency withstand voltage |
|
TZ 185 Z 02 |
IEC 60290, 3rd Ed
1990-12
IEC 60694, Ed2.2, 2002-01 |
Apr 2002 |
CT bushing insulation
75kV lightning impulse withstand test 28kV power frequency withstand
voltage |
|
TZ 185 Z 03 |
Shell DEP |
Apr 2002 |
1-hour power frequency
withstand voltage test of standard busbar insulation. 1hr @
11kV then 1hr @ 13.8kV then 1hr @ 17kV (3hr test). |
|
SD200407-001 |
BS EN 60529:1992 |
Jul 2006 |
IP5X - Probe and Dust ingress
Para 13.4, 13.5 Dust category 1. |
|
SD200407-002 |
BS EN 60529:1992 |
Jul 2006 |
IP4X - Water ingress
Para 14.2.4(b), fig 5 nozzle-spray. |
|
16705 |
BS EN 60439-1:1999 |
Oct 2007 |
2 x 100 x 10mm Main Busbar & 3200A 4P ACB through fault.
80kA, 1s. 176kA peak, 3Ph.
48kA, 1s, 101kA peak, Ph-N.
1 x 50 x 10mm Main Earth Bar.
48kA, 1s. 101kA peak, Ph-E. |
|
16706 |
BS EN 60439-1:1999 |
Oct 2007 |
1 x 50.8 x 6.35mm Main Busbar & 800A 4P ACB through fault.
50kA, 1s 105kA peak, 3Ph.
30kA, 1s. 63kA peak, Ph - N.
1 x 50.8 x 6.35mm Main Earth Bar.
30kA, 1s. 63kA peak, Ph - N.
Conditional SC test @ 415V, 3Ph, 50kA, 105kA peak, Pf=0.25
800A 4P, ACB (fault make test - open routine).
11kW, 30kW, 55kW Intelligent DOL Starters (fuselink rupture).
160A, 250A, 400A MCCBs (MCCB fault trip routine). |
Note: FBA = Factory Built Assembly
Click here to view an example of an ASTA Certificate
This list gives an overall picture of the Company’s commitment to test and
certification, which is an ongoing development. Customer
specific requirements can be considered when formulating our future test
schedules.
Note
Type tests are expensive to conduct but they are vital and are the only way of verifying the design in accordance with the requirements for TTA’s.
|